12/16/20/22.4 MVA substation transformer, 67 kV delta to 13.2 kV wye, with load tap changer
Price on request
A 12 MVA three-phase transformer carries 1,665 A at 4.16 kV, 556 A at 12.47 kV and 502 A at 13.8 kV at full load.
Every unit is tested before it ships and delivered by us.
Price on request
Price on request
Price on request
Price on request
Price on request
2 available
Price on request
5 available
Price on request
Price on request
Price on request
Price on request
Price on request
Price on request
Price on request
Price on request
Price on request
Price on request
Price on request
Price on request
Price on request
Price on request
Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.
| Voltage | Full-load current |
|---|---|
| 2.4 kV | 2,887 A |
| 4.16 kV | 1,665 A |
| 12.47 kV | 556 A |
| 13.2 kV | 525 A |
| 13.8 kV | 502 A |
| 24.94 kV | 278 A |
| 34.5 kV | 201 A |
| 69 kV | 100 A |
| 115 kV | 60.2 A |
| 138 kV | 50.2 A |
Work it out at another voltage with the kVA to amps calculator.
A 12 MVA three-phase transformer carries 1,665 A at 4.16 kV, 556 A at 12.47 kV and 502 A at 13.8 kV at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 12,000,000 VA ÷ (1.732 × 4160 V) = 1,665 A.
Arcbarn has 20 listings, by makers including Westinghouse, GE and Virginia Transformer. All 20 are priced on request.
The 8 listed here with a weight run from 27,650 lb to 112,854 lb.
Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor and capacitance; oil sample: dissolved gas analysis and dielectric strength; tap changer inspection and operation. You see the report before you buy.