7 MVA substation transformer, 12.47 kV delta to 4.16 kV wye
Price on request
A 7000 kVA three-phase transformer carries 8,420 A at 480 V, 6,736 A at 600 V and 972 A at 4.16 kV at full load.
Every unit is tested before it ships and delivered by us.
Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.
| Voltage | Full-load current |
|---|---|
| 480Y/277 V | 8,420 A |
| 600Y/347 V | 6,736 A |
| 2.4 kV | 1,684 A |
| 4.16 kV | 972 A |
| 12.47 kV | 324 A |
| 13.2 kV | 306 A |
| 13.8 kV | 293 A |
| 24.94 kV | 162 A |
| 34.5 kV | 117 A |
| 69 kV | 58.6 A |
| 115 kV | 35.1 A |
| 138 kV | 29.3 A |
Work it out at another voltage with the kVA to amps calculator.
A 7000 kVA three-phase transformer carries 8,420 A at 480 V, 6,736 A at 600 V and 972 A at 4.16 kV at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 7,000,000 VA ÷ (1.732 × 480 V) = 8,420 A.
Arcbarn has 3 listings, by makers including Westinghouse and Howard Industries. All 3 are priced on request.
Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor and capacitance; oil sample: dissolved gas analysis and dielectric strength; tap changer inspection and operation. You see the report before you buy.