1000/1120 kVA liquid-filled transformer, 12.47 kV delta to 480Y/277 V
Price on request
A 1000 kVA three-phase transformer carries 1,203 A at 480 V, 962 A at 600 V and 139 A at 4.16 kV at full load.
Every unit is tested before it ships and delivered by us.
Price on request
Price on request
Price on request
Price on request
$38,500
Price on request
$24,480
$12,000
$16,000
Price on request
2 available
Price on request
Price on request
2 available
Price on request
Price on request
Price on request
Price on request
Price on request
Price on request
11 available
$55,000
Price on request
$28,800
$10,500
Price on request
Price on request
Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.
| Voltage | Full-load current |
|---|---|
| 480Y/277 V | 1,203 A |
| 600Y/347 V | 962 A |
| 2.4 kV | 241 A |
| 4.16 kV | 139 A |
| 12.47 kV | 46.3 A |
| 13.2 kV | 43.7 A |
| 13.8 kV | 41.8 A |
| 24.94 kV | 23.1 A |
| 34.5 kV | 16.7 A |
| 69 kV | 8.4 A |
| 115 kV | 5 A |
| 138 kV | 4.2 A |
Work it out at another voltage with the kVA to amps calculator.
A 1000 kVA three-phase transformer carries 1,203 A at 480 V, 962 A at 600 V and 139 A at 4.16 kV at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 1,000,000 VA ÷ (1.732 × 480 V) = 1,203 A.
Arcbarn has 27 listings, by makers including GE, Square D and Cooper. Listed prices run from $10,500 to $55,000, and 20 are priced on request.
The 7 listed here with a weight run from 5,575 lb to 10,000 lb.
Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor and capacitance; oil sample: dissolved gas analysis and dielectric strength; tap changer inspection and operation. You see the report before you buy.