54/79/90 MVA substation transformer, 66 kV delta to 34.5 kV GrdY, with load tap changer
Price on request
A 54 MVA three-phase transformer carries 7,494 A at 4.16 kV, 2,500 A at 12.47 kV and 2,259 A at 13.8 kV at full load.
Every unit is tested before it ships and delivered by us.
Price on request
Price on request
Price on request
Price on request
Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.
| Voltage | Full-load current |
|---|---|
| 4.16 kV | 7,494 A |
| 12.47 kV | 2,500 A |
| 13.2 kV | 2,362 A |
| 13.8 kV | 2,259 A |
| 24.94 kV | 1,250 A |
| 34.5 kV | 904 A |
| 69 kV | 452 A |
| 115 kV | 271 A |
| 138 kV | 226 A |
Work it out at another voltage with the kVA to amps calculator.
A 54 MVA three-phase transformer carries 7,494 A at 4.16 kV, 2,500 A at 12.47 kV and 2,259 A at 13.8 kV at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 54,000,000 VA ÷ (1.732 × 4160 V) = 7,494 A.
Arcbarn has 4 listings, by makers including WEG and Siemens Energy. All 4 are priced on request.
Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor and capacitance; oil sample: dissolved gas analysis and dielectric strength; tap changer inspection and operation. You see the report before you buy.