66/88/110 MVA substation transformer, 69 kV wye to 34.5 kV wye
Price on request
A 66 MVA three-phase transformer carries 9,160 A at 4.16 kV, 3,056 A at 12.47 kV and 2,761 A at 13.8 kV at full load.
Every unit is tested before it ships and delivered by us.
Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.
| Voltage | Full-load current |
|---|---|
| 4.16 kV | 9,160 A |
| 12.47 kV | 3,056 A |
| 13.2 kV | 2,887 A |
| 13.8 kV | 2,761 A |
| 24.94 kV | 1,528 A |
| 34.5 kV | 1,104 A |
| 69 kV | 552 A |
| 115 kV | 331 A |
| 138 kV | 276 A |
Work it out at another voltage with the kVA to amps calculator.
A 66 MVA three-phase transformer carries 9,160 A at 4.16 kV, 3,056 A at 12.47 kV and 2,761 A at 13.8 kV at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 66,000,000 VA ÷ (1.732 × 4160 V) = 9,160 A.
Arcbarn has 3 listings, by makers including Fortune Electric, Kolektor Etra and Virginia Transformer. All 3 are priced on request.
Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor and capacitance; oil sample: dissolved gas analysis and dielectric strength; tap changer inspection and operation. You see the report before you buy.