72/96/120 MVA substation transformers, 138 kV wye to 34.5 kV wye
Price on request
2 available
A 72 MVA three-phase transformer carries 9,993 A at 4.16 kV, 3,334 A at 12.47 kV and 3,012 A at 13.8 kV at full load.
Every unit is tested before it ships and delivered by us.
Price on request
2 available
Price on request
Price on request
Price on request
Price on request
2 available
Price on request
Price on request
3 available
Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.
| Voltage | Full-load current |
|---|---|
| 4.16 kV | 9,993 A |
| 12.47 kV | 3,334 A |
| 13.2 kV | 3,149 A |
| 13.8 kV | 3,012 A |
| 24.94 kV | 1,667 A |
| 34.5 kV | 1,205 A |
| 69 kV | 602 A |
| 115 kV | 361 A |
| 138 kV | 301 A |
Work it out at another voltage with the kVA to amps calculator.
A 72 MVA three-phase transformer carries 9,993 A at 4.16 kV, 3,334 A at 12.47 kV and 3,012 A at 13.8 kV at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 72,000,000 VA ÷ (1.732 × 4160 V) = 9,993 A.
Arcbarn has 7 listings, by makers including Hitachi, Siemens and ABB. All 7 are priced on request.
Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor and capacitance; oil sample: dissolved gas analysis and dielectric strength; tap changer inspection and operation. You see the report before you buy.