132/176/220 MVA step-up transformer, 34.5 kV to 345 kV
Price on request
A 132 MVA three-phase transformer carries 6,111 A at 12.47 kV, 5,522 A at 13.8 kV and 2,209 A at 34.5 kV at full load.
Every unit is tested before it ships and delivered by us.
Price on request
Price on request
Price on request
Price on request
Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.
| Voltage | Full-load current |
|---|---|
| 12.47 kV | 6,111 A |
| 13.2 kV | 5,774 A |
| 13.8 kV | 5,522 A |
| 24.94 kV | 3,056 A |
| 34.5 kV | 2,209 A |
| 69 kV | 1,104 A |
| 115 kV | 663 A |
| 138 kV | 552 A |
Work it out at another voltage with the kVA to amps calculator.
A 132 MVA three-phase transformer carries 6,111 A at 12.47 kV, 5,522 A at 13.8 kV and 2,209 A at 34.5 kV at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 132,000,000 VA ÷ (1.732 × 12470 V) = 6,111 A.
Arcbarn has 4 listings, by makers including ABB / Hitachi, Hyundai and JSHP. All 4 are priced on request.
Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor and capacitance; oil sample: dissolved gas analysis and dielectric strength; tap changer inspection and operation. You see the report before you buy.