12/13.44/22.4 MVA substation transformers, 115 kV delta to 24.94Y/14.4 kV

Substation transformerRefurbishedListing #2230Location on request

Year built
1975
In service
Not stated
Equipment no.
1771-1, 1771-2-BWD
Manufacturer
Westinghouse

Price and quote

Price on request2 available

Price for the equipment. Your quote adds testing and delivery to your site.

  • Tested before it ships, and you see the report first
  • Delivered to your site, with rigging and freight quoted up front
  • Confirmed with the seller before we quote
Drawing for illustration. Photos and the nameplate are available on request.

Specifications

Rating
12,000 kVA at 55 °C, 13,440 kVA at 65 °C; 22,400 kVA with added forced-air equipment
Primary
115,000 V delta
Secondary
24,940Y/14,400 V
Full-load current
278 A at 12 MVA, 311 A at 13.44 MVA and 519 A at 22.4 MVA, at 24.94 kV calculated from its rating
Phase
3-phase, 60 Hz
Tap changer
De-energized, five positions (120,750 to 109,250 V)
Impedance
7.4% at 12 MVA (faint stamping)
BIL
450 kV HV, 150 kV LV
Cooling
OA (type SL)
Fluid
Oil, about 3,426 gal
Weight
About 88,450 lb
Accessories
Six 600:5 multi-ratio HV CTs, three 1200:5 LV CTs, hot-spot CT

About this unit

Two reconditioned Westinghouse units sold together; the dealer posts one 1975 nameplate and says the second unit's data, serials and cooling equipment need confirming. Location, price and a technical package come with a quote, and the dealer says listings are subject to prior sale.