Full-load current of a 10 MVA transformer

Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.

VoltageFull-load current
600Y/347 V9,623 A
2.4 kV2,406 A
4.16 kV1,388 A
12.47 kV463 A
13.2 kV437 A
13.8 kV418 A
24.94 kV231 A
34.5 kV167 A
69 kV83.7 A
115 kV50.2 A
138 kV41.8 A

Work it out at another voltage with the kVA to amps calculator.

Questions about used 10 MVA substation transformers

How many amps is a 10 MVA transformer?

A 10 MVA three-phase transformer carries 9,623 A at 600 V, 1,388 A at 4.16 kV and 463 A at 12.47 kV at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 10,000,000 VA ÷ (1.732 × 600 V) = 9,623 A.

What 10 MVA substation transformers does Arcbarn have for sale?

Arcbarn has 28 listings, by makers including Virginia Transformer, ABB and Westinghouse. All 28 are priced on request.

How much does a 10 MVA substation transformer weigh?

The 12 listed here with a weight run from 51,560 lb to 106,700 lb.

What tests does Arcbarn run on a used 10 MVA substation transformer?

Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor and capacitance; oil sample: dissolved gas analysis and dielectric strength; tap changer inspection and operation. You see the report before you buy.