800 kVA dry-type transformers

A 800 kVA three-phase transformer carries 962 A at 480 V, 2,221 A at 208 V and 770 A at 600 V at full load.

Every unit is tested before it ships and delivered by us.

Full-load current of a 800 kVA transformer

Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.

VoltageFull-load current
208Y/120 V2,221 A
240 V1,925 A
480Y/277 V962 A
600Y/347 V770 A
2.4 kV192 A
4.16 kV111 A
12.47 kV37 A
13.2 kV35 A
13.8 kV33.5 A
24.94 kV18.5 A
34.5 kV13.4 A

Work it out at another voltage with the kVA to amps calculator.

Questions about used 800 kVA dry-type transformers

How many amps is a 800 kVA transformer?

A 800 kVA three-phase transformer carries 962 A at 480 V, 2,221 A at 208 V and 770 A at 600 V at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 800,000 VA ÷ (1.732 × 480 V) = 962 A.

What 800 kVA dry-type transformers does Arcbarn have for sale?

Arcbarn has 3 listings, by makers including Metalec. All 3 are priced on request.

What tests does Arcbarn run on a used 800 kVA dry-type transformer?

Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor; inspection of coils, connections and fans. You see the report before you buy.