500 kVA VPI dry-type transformer, 12.47 kV to 208Y/120 V
$7,500
A 500 kVA three-phase transformer carries 601 A at 480 V, 1,388 A at 208 V and 481 A at 600 V at full load.
Every unit is tested before it ships and delivered by us.
$7,500
$7,500
Price on request
Price on request
$12,740
$5,400
$5,400
$15,000
Price on request
Price on request
Price on request
Price on request
$7,500
$8,000
$10,000
$7,500 each
2 available
$7,500
Price on request
3 available
Price on request
4 available
Price on request
$8,500 each
2 available
$5,800
Price on request
Price on request
Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.
| Voltage | Full-load current |
|---|---|
| 208Y/120 V | 1,388 A |
| 240 V | 1,203 A |
| 480Y/277 V | 601 A |
| 600Y/347 V | 481 A |
| 2.4 kV | 120 A |
| 4.16 kV | 69.4 A |
| 12.47 kV | 23.1 A |
| 13.2 kV | 21.9 A |
| 13.8 kV | 20.9 A |
| 24.94 kV | 11.6 A |
| 34.5 kV | 8.4 A |
Work it out at another voltage with the kVA to amps calculator.
A 500 kVA three-phase transformer carries 601 A at 480 V, 1,388 A at 208 V and 481 A at 600 V at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 500,000 VA ÷ (1.732 × 480 V) = 601 A.
Arcbarn has 31 listings, by makers including Federal Pacific, GE and Hammond. Listed prices run from $5,400 to $15,000, and 17 are priced on request.
The 14 listed here with a weight run from 2,000 lb to 6,500 lb.
Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor; inspection of coils, connections and fans. You see the report before you buy.