2000 kVA dry-type transformers

A 2000 kVA three-phase transformer carries 2,406 A at 480 V, 5,551 A at 208 V and 1,925 A at 600 V at full load.

Every unit is tested before it ships and delivered by us.

56 listings, page 1 of 3

Full-load current of a 2000 kVA transformer

Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.

VoltageFull-load current
208Y/120 V5,551 A
240 V4,811 A
480Y/277 V2,406 A
600Y/347 V1,925 A
2.4 kV481 A
4.16 kV278 A
12.47 kV92.6 A
13.2 kV87.5 A
13.8 kV83.7 A
24.94 kV46.3 A
34.5 kV33.5 A

Work it out at another voltage with the kVA to amps calculator.

Questions about used 2000 kVA dry-type transformers

How many amps is a 2000 kVA transformer?

A 2000 kVA three-phase transformer carries 2,406 A at 480 V, 5,551 A at 208 V and 1,925 A at 600 V at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 2,000,000 VA ÷ (1.732 × 480 V) = 2,406 A.

What 2000 kVA dry-type transformers does Arcbarn have for sale?

Arcbarn has 56 listings, by makers including Westinghouse, GE and Cutler-Hammer. Listed prices run from $4,200 to $57,600 each, and 39 are priced on request.

How much does a 2000 kVA dry-type transformer weigh?

The 23 listed here with a weight run from 4,717 lb to 19,700 lb.

What tests does Arcbarn run on a used 2000 kVA dry-type transformer?

Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor; inspection of coils, connections and fans. You see the report before you buy.