100 kVA dry-type transformers

A 100 kVA three-phase transformer carries 120 A at 480 V, 278 A at 208 V and 96.2 A at 600 V at full load.

Every unit is tested before it ships and delivered by us.

Full-load current of a 100 kVA transformer

Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.

VoltageFull-load current
208Y/120 V278 A
240 V241 A
480Y/277 V120 A
600Y/347 V96.2 A
2.4 kV24.1 A
4.16 kV13.9 A
12.47 kV4.6 A
13.2 kV4.4 A
13.8 kV4.2 A
24.94 kV2.3 A
34.5 kV1.7 A

Work it out at another voltage with the kVA to amps calculator.

Questions about used 100 kVA dry-type transformers

How many amps is a 100 kVA transformer?

A 100 kVA three-phase transformer carries 120 A at 480 V, 278 A at 208 V and 96.2 A at 600 V at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 100,000 VA ÷ (1.732 × 480 V) = 120 A.

What 100 kVA dry-type transformers does Arcbarn have for sale?

Arcbarn has 4 listings, by makers including GE, Federal Pacific and Square D. Listed prices run from $2,500 each to $2,950, and 2 are priced on request.

What tests does Arcbarn run on a used 100 kVA dry-type transformer?

Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor; inspection of coils, connections and fans. You see the report before you buy.