1250 kVA dry-type transformers

A 1250 kVA three-phase transformer carries 1,504 A at 480 V, 3,470 A at 208 V and 1,203 A at 600 V at full load.

Every unit is tested before it ships and delivered by us.

Full-load current of a 1250 kVA transformer

Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.

VoltageFull-load current
208Y/120 V3,470 A
240 V3,007 A
480Y/277 V1,504 A
600Y/347 V1,203 A
2.4 kV301 A
4.16 kV173 A
12.47 kV57.9 A
13.2 kV54.7 A
13.8 kV52.3 A
24.94 kV28.9 A
34.5 kV20.9 A

Work it out at another voltage with the kVA to amps calculator.

Questions about used 1250 kVA dry-type transformers

How many amps is a 1250 kVA transformer?

A 1250 kVA three-phase transformer carries 1,504 A at 480 V, 3,470 A at 208 V and 1,203 A at 600 V at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 1,250,000 VA ÷ (1.732 × 480 V) = 1,504 A.

What 1250 kVA dry-type transformers does Arcbarn have for sale?

Arcbarn has 9 listings, by makers including Hammond, Eaton and Hammond Manufacturing. The listed price is $9,751, and 8 are priced on request.

What tests does Arcbarn run on a used 1250 kVA dry-type transformer?

Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor; inspection of coils, connections and fans. You see the report before you buy.