5000 kVA pad-mount transformers

A 5000 kVA three-phase transformer carries 6,014 A at 480 V, 4,811 A at 600 V and 694 A at 4.16 kV at full load.

Every unit is tested before it ships and delivered by us.

Full-load current of a 5000 kVA transformer

Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.

VoltageFull-load current
480Y/277 V6,014 A
600Y/347 V4,811 A
4.16 kV694 A
12.47 kV231 A
13.2 kV219 A
13.8 kV209 A
24.94 kV116 A
34.5 kV83.7 A

Work it out at another voltage with the kVA to amps calculator.

Questions about used 5000 kVA pad-mount transformers

How many amps is a 5000 kVA transformer?

A 5000 kVA three-phase transformer carries 6,014 A at 480 V, 4,811 A at 600 V and 694 A at 4.16 kV at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 5,000,000 VA ÷ (1.732 × 480 V) = 6,014 A.

What 5000 kVA pad-mount transformers does Arcbarn have for sale?

Arcbarn has 12 listings, by makers including Westinghouse, GE and Maddox Industrial Transformer. Listed prices run from $58,800 to $62,328, and 9 are priced on request.

How much does a 5000 kVA pad-mount transformer weigh?

The 3 listed here with a weight run from 19,473 lb to 26,682 lb.

What tests does Arcbarn run on a used 5000 kVA pad-mount transformer?

Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor and capacitance; oil sample: dissolved gas analysis and dielectric strength. You see the report before you buy.