1500 kVA pad-mount transformers

A 1500 kVA three-phase transformer carries 1,804 A at 480 V, 4,164 A at 208 V and 1,443 A at 600 V at full load.

Every unit is tested before it ships and delivered by us.

45 listings, page 1 of 2

Full-load current of a 1500 kVA transformer

Three-phase, at the usual line-to-line voltages: the rating in VA divided by √3 and the voltage.

VoltageFull-load current
208Y/120 V4,164 A
240 V3,608 A
480Y/277 V1,804 A
600Y/347 V1,443 A
4.16 kV208 A
12.47 kV69.4 A
13.2 kV65.6 A
13.8 kV62.8 A
24.94 kV34.7 A
34.5 kV25.1 A

Work it out at another voltage with the kVA to amps calculator.

Questions about used 1500 kVA pad-mount transformers

How many amps is a 1500 kVA transformer?

A 1500 kVA three-phase transformer carries 1,804 A at 480 V, 4,164 A at 208 V and 1,443 A at 600 V at full load. Full-load current is the rating divided by √3 times the line-to-line voltage: 1,500,000 VA ÷ (1.732 × 480 V) = 1,804 A.

What 1500 kVA pad-mount transformers does Arcbarn have for sale?

Arcbarn has 45 listings, by makers including ABB, GE and GE Prolec. Listed prices run from $11,200 to $54,900, and 36 are priced on request.

How much does a 1500 kVA pad-mount transformer weigh?

The 12 listed here with a weight run from 6,900 lb to 16,800 lb.

What tests does Arcbarn run on a used 1500 kVA pad-mount transformer?

Every unit is tested before it ships: turns ratio (TTR) on every tap; insulation resistance; winding resistance; power factor and capacitance; oil sample: dissolved gas analysis and dielectric strength. You see the report before you buy.