3000/4000 kVA dry-type transformer, 13.8 kV delta to 4.16 kV delta

Dry-type transformerCondition not statedListing #2497Location on request

Year built
Not stated
In service
Not stated
Equipment no.
DT2006
Manufacturer
Square D

Price and quote

Price on request

Price for the equipment. Your quote adds testing and delivery to your site.

  • Tested before it ships, and you see the report first
  • Delivered to your site, with rigging and freight quoted up front
  • Confirmed with the seller before we quote
Drawing for illustration. Photos and the nameplate are available on request.

Specifications

Rating
3,000/4,000 kVA, 150 °C rise, AA/FA
Primary
13,800 V delta
Secondary
4,160 V delta
Full-load current
416 A at 3000 kVA and 555 A at 4000 kVA, at 4.16 kV calculated from its rating
Phase
3-phase, 60 Hz
Impedance
5.85%
Taps
14,490, 14,145, 13,800, 13,455 and 13,110 V
BIL
95 kV HV, 30 kV LV
Windings
Aluminum
Enclosure
Indoor
Weight
14,550 lb

About this unit

Square D indoor dry-type substation unit stepping 13.8 kV down to 4,160 V delta, stocked by RESA Power and offered as is or remanufactured; the page's contact is its Cerritos, California branch. No year, condition, unit location or price is given.

Listed October 18, 2026

More dry-type transformers