100/133.333/166.667 MVA substation transformer, 120 kV delta to 24.9Y/14.376 kV, with load tap changer

Substation transformerNew surplusListing #2395USA

Year built
2015
In service
Never energized
Equipment no.
JJ-WEG-120-167
Manufacturer
WEG

Price and quote

Price on request

Price for the equipment. Your quote adds testing and delivery to your site.

  • Tested before it ships, and you see the report first
  • Delivered to your site, with rigging and freight quoted up front
  • Confirmed with the seller before we quote
Drawing for illustration. Photos and the nameplate are available on request.

Specifications

Rating
100/133.333/166.667 MVA, KNAN/KNAF/KNAF
Primary
120,000 V delta
Secondary
24,900Y/14,376 V
Full-load current
2,319 A at 100 MVA, 3,092 A at 133.33 MVA and 3,864 A at 166.67 MVA, at 24.9 kV calculated from its rating
Phase
3-phase, 60 Hz
Vector group
Dyn1
Tap changer
HV on-load, 108 to 132 kV, 16 raise and 16 lower steps of 0.625%
BIL
550 kV HV winding, 150 kV LV
Cooling
KNAN/KNAF/KNAF
Weight
316,572 lb total (nameplate)

About this unit

Never-energized WEG power regulating transformer built in 2015 and stored in the USA, offered by broker J&J Transformers with availability confirmed on September 24, 2026. Nominal impedance, fluid specification and test reports still need confirming from the nameplate and records. Price on request.

Listed October 18, 2026

More substation transformers