16/21.3/26.7 MVA substation transformer, 46 kV delta to 12.47Y/7.2 kV, with load tap changer

Substation transformerCondition not statedListing #2392Garden City, KS

Year built
Not stated
In service
Not stated
Equipment no.
JJ-TX-104
Manufacturer
Virginia Transformer

Price and quote

Price on request

Price for the equipment. Your quote adds testing and delivery to your site.

  • Tested before it ships, and you see the report first
  • Delivered to your site, with rigging and freight quoted up front
  • Confirmed with the seller before we quote
Drawing for illustration. Photos and the nameplate are available on request.

Specifications

Rating
16/21.33/26.7 MVA, ONAN/ONAF/ONAF, 65 °C rise
Primary
46,000 V delta
Secondary
12,470GrdY/7,200 V
Full-load current
741 A at 16 MVA, 986 A at 21.3 MVA and 1,236 A at 26.7 MVA, at 12.47 kV calculated from its rating
Phase
3-phase, 60 Hz
Vector group
Dyn1
Tap changer
Load tap changer, ±16 × 0.625%, 33 positions
Impedance
7.50% nominal (outline drawing)
BIL
250 kV HV, 110 kV LV
Windings
Copper
Weight
124,150 lb nominal (outline drawing)

About this unit

Virginia Transformer unit reported in storage at Garden City, Kansas, listed by broker J&J Transformers from a supplier schedule received October 8, 2026. Construction reportedly began in 2022 and the supplier cited a warranty to July 2029, but condition, final impedance and weight still need confirming. Price on request.

Listed October 18, 2026

More substation transformers

View all substation transformers