6000 kVA unit substation transformer, 44 kV to 600Y/347 V

Substation transformerNew surplusListing #2248East Central Canada

Year built
2024
In service
Never energized; surplus from a cancelled project
Equipment no.
1673129
Manufacturer
Power Systems Technology, 23-375 MiniSub

Price and quote

Price on request

Price for the equipment. Your quote adds testing and delivery to your site.

  • Tested before it ships, and you see the report first
  • Delivered to your site, with rigging and freight quoted up front
  • Confirmed with the seller before we quote
Drawing for illustration. Photos and the nameplate are available on request.

Specifications

Rating
6,000 kVA, ONAN, 60 °C oil / 65 °C winding rise
Primary
44,000 V
Secondary
600Y/347 V
Full-load current
5,774 A at 600 V calculated from its rating
Phase
3-phase, 60 Hz
Impedance
7% at 6,000 kVA
BIL
250 kV HV, 30 kV LV
Fluid
Non-PCB mineral oil, 4,070 L
Windings
Copper
Cooling
ONAN
Weight
15,580 kg
Dimensions
3,546 × 2,906 × 2,733 mm (L × W × H)
Accessories
Built-in NEMA 3R low-voltage switchgear with three 2000 A ABB LSIG breakers; separate 600 V distribution with two 2000 A switchboards, four 1200 A panels and a 600 A panelboard

About this unit

Unused 2024 oil-filled MiniSub with built-in low-voltage switchgear, factory built, tested and hipot tested, now surplus from a cancelled project. A British Columbia reseller offers it from east-central Canada; price is on request.

Listed October 18, 2026