1500/2000 kVA liquid-filled transformers, 27.6 kV delta to 600Y/347 V

Substation transformerUsedListing #2166Location on request

Year built
2001
In service
Not stated
Equipment no.
INV 56
Manufacturer
Stein

Price and quote

Price on request2 available

Price for the equipment. Your quote adds testing and delivery to your site.

  • Tested before it ships, and you see the report first
  • Delivered to your site, with rigging and freight quoted up front
  • Confirmed with the seller before we quote
Drawing for illustration. Photos and the nameplate are available on request.

Specifications

Rating
1,500/2,000 kVA, LNAN/LNAF, 65 °C rise
Primary
27,600 V delta
Secondary
600/347 V, wye
Full-load current
1,443 A at 1500 kVA and 1,925 A at 2000 kVA, at 600 V calculated from its rating
Vector group
D-y
Impedance
5.7% / 7.6%
BIL
150 kV HV, 45 kV LV
Cooling
LNAN/LNAF
Fluid
Liquid, 1,500 L each
Weight
6,000 kg and 5,900 kg

About this unit

Two pre-owned 2001 Stein units with consecutive serials and LNAN/LNAF cooling, listed as INV 56 and 58. LTL, a Toronto supplier of utility safety and testing gear, lists them in its pre-owned transformer table and asks buyers to call for pricing. The table doesn't say whether they're a pad-mount or station type or where they sit (LTL has sites in Toronto, Edmonton and Surrey, BC).

Listed October 18, 2026

More substation transformers