2000/2667 kVA oil-filled transformers, 27.6 kV delta to 600Y/347 V

Substation transformerUsedListing #2163Location on request

Year built
1980
In service
Not stated
Equipment no.
INV 40
Manufacturer
Federal Pioneer

Price and quote

Price on request2 available

Price for the equipment. Your quote adds testing and delivery to your site.

  • Tested before it ships, and you see the report first
  • Delivered to your site, with rigging and freight quoted up front
  • Confirmed with the seller before we quote
Drawing for illustration. Photos and the nameplate are available on request.

Specifications

Rating
2,000/2,667 kVA, ONAN/ONAF, 65 °C rise
Primary
27,600 V delta
Secondary
600/347 V, wye
Full-load current
1,925 A at 2000 kVA and 2,566 A at 2667 kVA, at 600 V calculated from its rating
Vector group
D-y
Impedance
5.5% (INV 40) and 5.46% (INV 41)
Cooling
ONAN/ONAF
Fluid
Oil, 510 gal each
Weight
17,100 lb each

About this unit

Two pre-owned 1980 Federal Pioneer units with consecutive serials and one drawing number, listed as INV 40 and 41. LTL, a Toronto supplier of utility safety and testing gear, lists them in its pre-owned transformer table and asks buyers to call for pricing. The BIL figures shown (500 kV HV, 10 kV LV) look like typos, so confirm them on the nameplates.

Listed October 18, 2026

More substation transformers

View all substation transformers