45/60/75 MVA substation transformer, 140 kV delta to 14Y/8.08 kV, with load tap changer

Substation transformerCondition not statedListing #2052Location on request

Year built
1983
In service
Not stated
Equipment no.
Not stated
Manufacturer
McGraw-Edison

Price and quote

$750,000

Price for the equipment. Your quote adds testing and delivery to your site.

  • Tested before it ships, and you see the report first
  • Delivered to your site, with rigging and freight quoted up front
  • Confirmed with the seller before we quote
Drawing for illustration. Photos and the nameplate are available on request.

Specifications

Rating
45,000/60,000/75,000 kVA, OA/FA/FA, 65 °C rise
Primary
140,000 V delta
Secondary
14,000Y/8,080 V
Full-load current
1,856 A at 45 MVA, 2,474 A at 60 MVA and 3,093 A at 75 MVA, at 14 kV calculated from its rating
Phase
3-phase, 60 Hz
Impedance
13.9% at 45 MVA
BIL
650 kV HV, 110 kV LV
Tap changer
Load tap changer on the secondary, 33 steps, 11,900 to 16,100 V
Taps
HV no-load taps from 133,000 to 147,000 V
Windings
Copper
Connection
Delta-wye
Weight
285,000 lb assembled with oil; 173,000 lb shipping weight without oil
Accessories
Fans and fan controls, gauge and valve package, multi-ratio bushing CTs

About this unit

1983 McGraw-Edison substation transformer with a 33-step load tap changer on the secondary, listed at a fixed price by RAAR Group USA, an equipment seller in Redondo Beach, California. The listing says it is in stock but doesn't say where it sits or what condition it is in.

Listed October 18, 2026

More substation transformers

View all substation transformers