5/6.25 MVA substation transformer, 13.8 kV delta to 4.16 kV wye

Substation transformerCondition not statedListing #2003Easton, PA

Year built
1998
In service
Not stated
Equipment no.
T-6215
Manufacturer
Westinghouse

Price and quote

Price on request

Price for the equipment. Your quote adds testing and delivery to your site.

  • Tested before it ships, and you see the report first
  • Delivered to your site, with rigging and freight quoted up front
  • Confirmed with the seller before we quote
Drawing for illustration. Photos and the nameplate are available on request.

Specifications

Rating
5,000/6,250 kVA, 65 °C rise
Primary
13,800 V delta
Secondary
4,160 V wye
Full-load current
694 A at 5000 kVA and 867 A at 6250 kVA, at 4.16 kV calculated from its rating
Phase
3-phase, 60 Hz
Cooling
OA/FA
Tap changer
Called LTC in the title; confirm the type
Taps
14,400 / 14,100 / 13,800 / 13,500 / 13,200 V
Impedance
5.64%
BIL
110 kV HV, 75 kV LV
Windings
Aluminum
Fluid
638 gal; type not stated
Arresters
15 kV HV, 5 kV LV
Weight
18,825 lb
Dimensions
190 × 124 × 163 in (L × W × H)

About this unit

1998 Westinghouse unit from a Pennsylvania dealer. The title says LTC, but the five taps listed look like a de-energized tap changer's, so confirm which. The fluid type isn't given; a unit built after July 1979 may be assumed non-PCB under EPA rules.

Listed October 16, 2026

More substation transformers

View all substation transformers