GuideTransformers9 min read
Buck-boost transformers
A buck-boost transformer raises (boosts) or lowers (bucks) a supply voltage by a small amount, usually 5 to 20%: 208 V up to 230 or 240 V, or 240 V down to 208 V. It’s a small two-winding transformer wired as an autotransformer, so a unit rated 1 to 5 kVA can correct the voltage for a 10 to 50 kVA load. It can’t isolate a circuit, create a neutral where there isn’t one, or hold a voltage that varies.
The short version
- Wired as an autotransformer, the low-voltage winding sits in series with the line and adds or subtracts its volts. The unit only carries the difference, which is why it’s a tenth the size of the load.
- Sizing, single-phase: buck-boost kVA = load amps × volts of boost (or buck) ÷ 1,000. A 30 A, 230 V load on a 208 V supply needs 30 × 21 ÷ 1,000 = 0.63 kVA: a 0.75 or 1 kVA unit.
- Typical uses: 230 V or 240 V equipment (air conditioners, imported machinery, motors) on a 208 V service, 208 V equipment on 240 V, and feeders that have dropped below 460 V at the far end.
- Three-phase: two units in open delta for a three-wire load, three units in wye when the neutral must carry through.
- Not for 480 V to 240 V, 480 V to 208 V, or any change beyond about 25%: those need a step-down transformer.
What a buck-boost transformer does
Equipment rated 230 V or 240 V turns up on 208 V services every day: rooftop air conditioners, commercial kitchen equipment, imported machines, motors rated 230/460 V. At 208 V a 230 V motor runs hot and loses torque, and a heating element delivers 18% less heat. The buck-boost transformer is the small, cheap fix: it lifts 208 V to about 229 V, or 236 V, and the equipment runs as rated. The same unit, connected the other way, lowers 240 V to 208 V, or 277 V to 240 V, or lifts 240 V to 277 V for lighting.
The trick is that it doesn’t transform the whole load. A conventional transformer between a 208 V supply and a 230 V load would have to be rated for the load’s full kVA. A buck-boost carries only the 21 V it adds, so a unit rated 1 kVA serves a 10 kVA load.
How it works: an autotransformer connection
A buck-boost is sold as an ordinary two-winding transformer: a primary rated 120 × 240 V and a secondary rated 12 × 24 V or 16 × 32 V, in sizes from 0.05 to 10 kVA. Wired as a two-winding unit it’s a small control or lighting transformer. Wired as a buck-boost, the primary goes across the supply and the secondary goes in series with the line to the load, so the secondary’s volts add to the supply (boost) or, with its leads reversed, subtract from it (buck).
Because the primary is rated 240 V and sees 208 V, the secondary gives 24 × 208 ÷ 240 = 20.8 V, and the output is 228.8 V. The current through the series winding is the load current, which is why the unit’s rating is set by the load amps and the boost volts rather than the load kVA.
Output volts = supply volts × (primary volts + secondary volts) ÷ primary volts
When to use one
| Supply | Equipment | Connection | Output |
|---|---|---|---|
| 208 V | Rated 230 or 240 V: air conditioners, heaters, 230 V motors | Boost, 24 V windings | 229 V |
| 208 V | Rated 240 V, sensitive to low voltage | Boost, 32 V windings | 236 V |
| 240 V | Rated 208 V: equipment moved from a 208 V building | Buck, 32 V windings | 212 V |
| 240 V | Rated 277 V lighting | Boost, 32 V windings | 272 V |
| 277 V | Rated 240 V | Buck, 32 V windings | 245 V |
| 440 to 460 V, at the end of a long feeder | Rated 480 V motors and drives | Boost, 24 or 32 V windings (480 V class units) | 480 V |
| 480 V | Rated 600 V (Canadian equipment) | Boost, 120 V windings | 600 V |
Outputs for a 240 V-rated primary; the exact figure scales with the supply voltage.
The last two rows are the industrial cases: a 480 V feeder that has sagged to 450 V by the time it reaches a pump house, or a 600 V machine bought from Canada. Buck-boost units are made in 480 V and 600 V classes for these, with 24, 32, 48 and 120 V secondaries.
How to size a buck-boost transformer
The unit has to carry the load current through its series winding at the boost (or buck) voltage. So, for single-phase:
Buck-boost kVA = load amps × boost volts ÷ 1,000
A 230 V air conditioner that draws 30 A, on a 208 V supply boosted by 21 V: 30 × 21 ÷ 1,000 = 0.63 kVA, so a 0.75 kVA unit (or 1 kVA, to leave margin). A conventional transformer for the same load would be 30 × 230 ÷ 1,000 = 6.9 kVA: a 7.5 kVA unit, ten times the size, weight and price.
Three checks before ordering:
- Use the load’s actual amps at the output voltage, from its nameplate, not an estimate; a motor’s full-load amps, and a safety factor for anything with a compressor.
- Confirm on the selection table. Every manufacturer publishes a table that, for each standard input and output voltage, lists the load amps each unit can carry. The table accounts for the exact winding ratios; use it to pick the catalog number and the connection diagram.
- Protect it as an autotransformer. NEC 450.4 sets the overcurrent protection at 125% of the autotransformer’s rated input current, which is the load current, not the small two-winding rating.
Three-phase: open delta or wye
Three-phase loads are boosted with two or three single-phase units, and the choice depends on the neutral.
| Connection | Units | Neutral | Use it for |
|---|---|---|---|
| Open delta | Two | None on the output | Three-wire loads: motors, compressors, three-phase heaters |
| Wye | Three | The supply neutral carries through | Four-wire loads, and any supply that has a neutral you must keep |
| Closed delta | Three | None | Rare; open delta does the job with one fewer unit |
A 208Y/120 V supply boosted in open delta gives a 229 V three-wire output with no usable neutral; boosted in wye it gives 229Y/132 V with its neutral intact. Sizing follows the same principle (the units carry the load current at the boost voltage), but the open-delta connection loads the two units unevenly, so the manufacturers’ three-phase tables are the way to pick them.
What a buck-boost can’t do
- Regulate. It adds a fixed percentage. A supply that swings swings the output with it. A site with a voltage problem rather than a voltage mismatch needs a regulator, or the utility.
- Isolate. The input and output share a conductor. Where isolation is the point (a separately derived system, noise, a floating supply for a machine), use a two-winding transformer.
- Make a neutral. It passes the supply neutral through (wye) or leaves it out (open delta); it can’t create one. For a 240 V three-wire delta supply that needs 120 V, the answer is a 240 V delta to 208Y/120 V transformer, not a buck-boost.
- Change voltage by more than about 25%. 480 V to 240 V, 480 V to 208 V, 240 V to 120 V: these are step-down transformers.
- Serve a load bigger than its table allows. The series winding’s ampacity is the limit, and it’s far lower than the load’s kVA suggests.
Buck-boost vs an isolation transformer
For a small correction on a load with a tolerant rating, a buck-boost is cheaper, smaller and more efficient than a two-winding transformer, and it’s the standard answer. A two-winding step-up or step-down transformer is the right one when the change is large, when the load needs its own grounded neutral, when isolation matters, or when the load is big enough that a 480 V to 208Y/120 V dry-type in the right size is the ordinary thing to buy. Those we sell; for buck-boost units in the 0.25 to 10 kVA range, an electrical distributor stocks them, and a Magic Search will turn up surplus ones.
Questions people ask
What does a buck-boost transformer do?
It changes a supply voltage by a small percentage, up (boost) or down (buck), to suit equipment rated for a different voltage: most often lifting a 208 V service to about 230 V for equipment rated 230 or 240 V, or dropping 240 V to 208 V. It’s a small transformer whose low-voltage winding is wired in series with the line, so it handles only the difference in voltage, not the whole load.
Can a buck-boost transformer change 208 V to 240 V?
To close to it. A unit with 12/24 V secondary windings connected to boost by 24 V on a 208 V supply gives 208 × (240 + 24) ÷ 240 = 229 V; with 16/32 V windings boosting by 32 V it gives 236 V. Both are within the range equipment rated 230 or 240 V accepts (usually ±10%). An exact 240 V isn’t available from a 208 V supply with standard windings, and isn’t needed.
How do I size a buck-boost transformer?
Single-phase: multiply the load’s full-load amps by the number of volts you’re adding or removing, and divide by 1,000; that’s the kVA the buck-boost must carry. A 40 A load boosted by 21 V needs 0.84 kVA, so a 1 kVA unit. Then confirm the choice on the manufacturer’s selection table, which lists each unit’s load capacity in amps for every standard input and output voltage. Three-phase sizing follows the same idea but depends on the connection, so use the table.
Can a buck-boost go from 480 V to 240 V?
No. That’s a 50% change, far beyond what the series winding of a buck-boost can do, and it would need a unit as large as a conventional transformer anyway. Use a 480 V to 240 V (or 480 V to 208Y/120 V) step-down transformer.
Does a buck-boost need a neutral?
A single-phase buck-boost doesn’t create or need a neutral: the supply’s grounded conductor passes straight through to the load. In three-phase, an open-delta pair serves a three-wire load and has no neutral on its output; a wye set of three units carries the supply neutral through to the load. The NEC (210.9) allows an autotransformer without a grounded conductor only for changing 208 V to 240 V or 240 V to 208 V.
Can a buck-boost transformer be used in reverse?
Yes. Buck is boost in reverse: the same unit raises 208 V to 229 V one way round and lowers 240 V to 218 V the other. The connection diagrams on the nameplate show both.
Is a buck-boost the same as a voltage regulator?
No. A buck-boost has a fixed ratio: it adds or subtracts the same percentage whatever the supply does. If the supply swings between 195 V and 220 V, the output swings with it. A voltage regulator (a tap-changing autotransformer or an electronic regulator) adjusts itself to hold the output steady.
Sources: NEC 210.9 and 450.4 (autotransformers); manufacturers’ buck-boost selection tables (Acme, Hammond, Square D, Eaton).